    [HAWK] - Configure the WNK81TP Temp/Pressure Sensor

    Written by Cameron Everett

    Updated at June 4th, 2024

      Contact Us

      If you still have questions or prefer to get help directly from an agent, please submit a request.
      We’ll get back to you as soon as possible.

      Contact Support
      • Home
      • Devices
      • Hawk IoT Datalogger
      • I²C

      Table of Contents

      Firmware Requirements Wiring Device Manager Configuration

      Firmware Requirements

      The WNK81TP requires:

      • Baseboard
        • FW v1.8+
      • Card
        • Agtech1 FW v1.12+ or 
        • Bluetooth Card FW v1.2+
       

      Wiring

      Wire as below:

      WNK81TP Agtech1 Bluetooth+
      VCC (Red) Hawk IO 5 Hawk IO 7
      SCL (Yellow)
       
      Hawk IO 6 Hawk IO 5
      SDA (White) Hawk IO 4 Hawk IO 6
      GND (Black) Hawk GND Hawk GND

      Device Manager Configuration

      1. Confirm you are on the correct Baseboard FW
        1. FW v1.8+
      2. Confirm you are on the correct Card FW
        1. For Agtech1 Card, FW v1.12+
        2. For BLE Card, FW v1.2+
      3. Add the I2C Action tab (see image below)
      4. Select the WNK81TP Pressure Temp Sensor option from the dropdown.
      1. I2C Address can be left at 0 to use the default address (which is 0xDA)
      2. Analog Offset can be set to the Analog you want to save the Pressure temperature to.
        1. The Temperature Value will be saved to the next one (i.e. Pressure in Analog 10, Temperature in Analog 11)
      3. Sensor Parameter 1: The Pressure mimimum.
      4. Sensor Parameter 2: The Pressure maximum. 
        1. e.g. if the max value the sensor can read is 10 Bar, set to 10,000 and divide out on the server side to get 5 significant figures.
      5. Sensor Parameter 3: Can be left as 0 to use the default Temperature address which is (0xFE)

       

      customize setup

      Was this article helpful?

      Yes
      No
      Give feedback about this article

      Related Articles

      • Configure I²C Sensor Readings
      • Hawk - Configure DM Ambient (Temp+Hum Sensor)

      Subscribe to Partner News

      Subscribe to our mailing list to receive Digital Matter news, product and tehnical updates, and more.

      Subscribe

      Copyright © Digital Matter . All Rights Reserved.

      Privacy Contact Support

      Knowledge Base Software powered by Helpjuice

      DM Logo
      Expand