Hawk - I²C SFA30 Formaldehyde Sensor Integration

Written by Cameron Everett

Updated at April 28th, 2025

Contact Us

If you still have questions or prefer to get help directly from an agent, please submit a request.
We’ll get back to you as soon as possible.

Contact Support
  • Home
  • Devices
  • Cellular
  • Data Loggers
  • Hawk IoT Datalogger
  • I²C

Table of Contents

Wiring Device Manager

Below are instructions for the I2C SFA30 Formaldehyde Sensor

Wiring

The sensor should have 4 wires.

VCC - Power line

SCL - Clock Line

SDA - Data Line

GND - Ground

Wire the appropriate wires into the appropriate IOs on the specific board of interest.

 

Agtech1

Bluetooth+

3v3

Hawk IO 5

Hawk IO 7

SCL

Hawk IO 6

Hawk IO 5

SDA

Hawk IO 4

Hawk IO 6

GND

Hawk GND

Hawk GND

Device Manager

This formaldehyde sensor takes 10s to warm up and for the readings to stabilize.

The sensor takes measurements every 0.5s.

When the device requests a reading, the sensor will return an average since the last reading request.

If the last request was more than a minute ago, the sensor returns a reading of approximately the last minute.

I2C Action params

Sensor Parameter 1 - Warmup time (s).

The device waits this long after powering the sensor, then does a reading to clear measurements during the power-up time (e.g. 10s).

Sensor Parameter 2 - Sampling time (s)

After doing reading 1, the device waits this amount of time. Then does another reading. The results of this second reading are logged.

E.g. Param1 = 10s, param2 = 5s. Warmup for 10s (required for formaldehyde reading) then sample for 5s and log the result (average of the 5s of sampling).

Alternate configuration

If Param1 is set to 0 and '3v3 always on' parameter is set to true, the device will skip the warmup and sampling times and just immediately do reading 2. The result will be the average from the last 60s or the average since the last time this action was run.

hawk formaldehyde sensor

Was this article helpful?

Yes
No
Give feedback about this article

Related Articles

  • Configure DS18B20 Temp Probe with Hawk
  • Hawk - Control Output from Server
  • Hawk Installation - Testing Sensor Readings
  • Hawk - Configure MLX90640 Infrared Camera

Subscribe to Partner News

Subscribe to our mailing list to receive Digital Matter news, product and tehnical updates, and more.

Subscribe

Copyright © Digital Matter . All Rights Reserved.

Privacy Contact Support

Knowledge Base Software powered by Helpjuice

Expand